Gas Fired Double-Effect Chiller-Heaters
CH-MG Series: 150 and 200 RT Cooling Capacities
MODEL | CH-MG150 |
CH-MG200 |
||
---|---|---|---|---|
Cooling | Capacity (Btu/hr x 1000) | 1,800 |
2,400 |
|
Chilled Water Temp. (°F) | 44.6 Outlet, 53.6 Inlet |
|||
Heating | Capacity (Btu/hr x 1000) | 1,245 |
1,660 |
|
Hot Water Temp. (°F) | 140.0 Outlet, 132.8 Inlet |
|||
Chilled/Hot Water | Rated Water Flow (gpm) | 399.4 |
532.6 |
|
Evap. Press. Loss (psi) | 10.5 |
9.2 |
||
Water Retention Volume (gal) | 48 |
69 |
||
Cooling Water | Heat Rejection (Btu/hr x 1000) | 3,045 |
4,060 |
|
Cooling Water Temp. (°F) | 85.1 Inlet, 94.3 Outlet |
|||
*Rated Water Flow (gpm) | 658.6 |
878.1 |
||
Cond./Abs. Press. Loss (psi) | 7.5 |
7.2 |
||
Water Retention Volume (gal) | 114 |
153 |
||
Fuel | Type | Natural Gas |
||
Input (Btu/hr x 1000) | Cooling | 1,500 |
2,000 |
|
Heating | 1,500 |
2,000 |
||
Electrical | Power Supply | 208V or 230V, 60Hz, 3ph |
||
Consumption (kVA) | Cooling | 2.9 |
3.3 |
|
Heating | 2.9 |
3.3 |
||
Control | Cooling and Heating | 30% - 100% PID Control |
||
Combustion | Type | Low NOx Forced Draft Burner |
||
Flame Detection | UV Scanner |
|||
Ignition | Intermittent Spark |
|||
Noise Level | Sound Pressure dB(A) | 74 |
74 |
|
Piping | Chilled/Hot Water (in) | 4 Flange |
5 Flange |
|
Cooling Water (in) | 5 Flange |
6 Flange |
||
Gas Supply (in) | 2 NPT |
2 NPT |
||
Exhaust Vent (in) | 13.8 x 9.8 (inside) |
|||
Weight | Dry (lb) | 12,346 |
14,330 |
|
Operating (lb) | 13,698 |
16,183 |
||
Cabinet | Type | Weatherproof |
||
Material | Pre-painted hot dipped galvanized steel |
|||
Finish | Silver metallic |
* Minimum cooling water flow